Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/WWM
Permit Number - T15CM02466
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/04/2015 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | T15CM02466 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL REQUIREMENTS: The City of Tucson adopted the 2012 IRC with amendments on 1/1/2012. Show the current code reference on the plans. GENERAL COMMENTS: 1. Show compliance with the Inclusive Home Design Ordinance adopted by the City of Tucson Ordinance #10463 on 10/16/2007. Notate an accessible door with a maximum ½" threshold height, a 30" minimum net interior door width, lever-type door hardware, electrical outlet reachable range of 15" - 48" above floor, grab bar reinforcement of 2"x6" blocking at the toilet, tub and shower 36" above floor, and a second row at the tub 9" above the tub rim. SECTIONS - DETAILS: 1. Show fiber-cement board or glass mat gypsum backers for tiled walls in tub and shower areas, R702.4.2. PLUMBING PLANS: 1. Show hot water pipe with minimum R-3 insulation, N1103.4.2. 2. Provide a water hammer arrester for quick-closing valves serving the clothes washer, P2903.5. MECHANICAL PLANS: 1. Provide (an HVAC system with) whole-house mechanical ventilation with continuous or a minimum controlled intermittent airflow rate, R303.4 & M1507.3. Show a source of outside supply air. ELECTRICAL PLANS: 1. Show or notate the requirement for a carbon monoxide detector outside of bedroom doors, when the dwelling includes an attached garage or gas appliance, R315. 2. Designate the circuit number at the location of each light fixture, receptacle, appliance and equipment disconnect switch, E3404.12. Update the clothes washer and wet bar circuits to be consistent with the panel schedule. 3. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, E3703.2 and E4001.3.1 through E4001.4.5. Update circuit #15 to 20 AMP. 4. Protect all interior 15A & 20A proposed outlets (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors with combination type arc-fault circuit interrupters, E3902.12. 5. Provide notation requiring tamper resistant receptacles for 125 volt, 15A and 20A receptacles, R4002.14. 6. Show or notate a disconnect means or a locking breaker for the water heater, E4101.5. 7. Specify high-efficacy lamps for at least 75% of all lighting fixtures, N1104.1. INTERNATIONAL ENERGY CONSERVATION CODE: 1. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing is U=0.40, skylights U=0.65, ceiling R=38 and walls R=13, N1102.1. Update note #9 sheet #2. If you have any questions please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/05/2015 | EGALLET1 | APPROVAL SHELF | Completed |
11/05/2015 | EGALLET1 | OUT TO CUSTOMER | Completed |
11/05/2015 | EGALLET1 | REJECT SHELF | Completed |