Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T15CM02319
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/16/2015 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/28/2015 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 04/30/2015 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | GENERAL 1. Please provide an approved site plan. 2. In the structural calculations: a. Please provide accurate and clear foundation and framing key plans showing the location of all calculated structural members. b. Please provide structural details and calculations for the following: All roof top mounted HVAC units and light pole foundations. SHEET CS 3. List of Adopted Building Codes for the City of Tucson a. Delete the listed 2009 IFC and use instead the 2012 IFC. b. In all drawings and code references, please delete the reference to ADA. The adopted accessibility code is the 2012 IBC, Chapter 11 and the 2009 ICC A117.1. Insure all accessibility details comply with these code requirements. 4. For accurate costs analysis and fee determination, please provide a cost breakdown as listed below: a. There are four existing building that show various items of repair and alteration. Please provide a cost estimate for these alterations for buildings "D" and "F". 5. It would be nice to have a partition schedule and full height architectural wall sections. SHEET A0 6. The building code analysis for each building states that sprinkler systems are not required. However, the plumbing plans clearly show fire sprinkler risers for building A and B and none for the rest of the buildings. Please explain. SHEET A1 7. For the drive ramps at the Maintenance Shop, the Fenced Yard and the Tool Storage, provide a 5' wide accessible route accross the front of all drives with a running slope not to exceed 5% and a cross slope not to exceed 2%. Place the drive ramp at the outter edge of the accessible route. 8. For all side walk ramps shown on the floor plans, provide an up/down directional arrow with a 1:12 max slope requirement note. 9. What's the purpose of the two ramps and landing at the NE corner of the tool storage building? 10. As per the toilet fixture calculations shown on sheet A0, the women's toilet is to be provided 3 w.c. and 2 Lavs. What is shown on the drawing floor plan and elevation is 2 w.c. and 1 urnial and 2 lavs. What's up Doc? 11. All accessible route slopes are to comply with the 2009 ICC A1171.1, Section 403.3; 5% maximum running slope and 2% cross slopes. Please provide a note on the drawings to that effect. SHEET A2 12. What looks like a tilt up concrete exterior wall panel is not identified nor is it on the wall legend. Please clarify. SHEET A6 13. At detail 3, if the urinal wall panels are deeper than 2'-0", the urinal stall must be 3'-0" wide. Please reconcile by provideing a dimension on the urinal panels. 14. All details have incorrect scale references. Please reconcile. SHEETS A9 THROUGH A12 15. Call out all exterior finishes. SHEET A13 16. Call out all roofing types. 17. Provide roof slope and direction on plans where they are not shown. END OF REVIEW |
| 05/01/2015 | RONALD BROWN | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
| 05/04/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide energy code compliance calculations for the building envelope, interior lighting, and mechanical systems. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C103.2 and C401.2, International Energy Conservation Code 2012. 2. Provide NFRC fenestration product ratings for the U-factor and the SHGC values on COMcheck or use the appropriate default U-factor and SHGC values from Tables C303.1.3 (1), C303.1.3 (2) and C303.1.3.(3), IECC 2012. Reference: Section C303.1.3, IECC 2012. 3. Show how the "Additional Efficiency Package Requirements" noted in COMcheck (C406, IECC 2012) is to be accomplished for the addition. Reference: Section C401.2, IECC 2012. 4. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012. 5. Verify the electrical requirements (e.g. the voltage) of the two PTAC units. Reference: Section 107.2.1, IBC2012. |
| 05/04/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide the dimensions of the rain gutter and downspouts. Reference: Section 1106.6, IPC 2012. |
| 05/04/2015 | ROBERT SHERRY | WATER | REVIEW | Passed | |
| 05/07/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/11/2015 | AROMERO4 | OUT TO CUSTOMER | Completed |