Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T15CM02297
Parcel: 10512020C

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T15CM02297
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. No information has been submitted to show that the installation of the vacuum relief valve for the water heater on the hot water supply pipe complies with the manufacturer's listing requirements. [Initial comment: Provide information to show that the installation of the vacuum relief valve for the water heater on the hot water supply pipe complies with the manufacturer's listing requirements. Reference: Section 303.2, IPC 2012.]
2. Revise the specification of the automatic faucet to require the cycle time to be adjusted to a minimum of ten seconds per Section 606.4, ANSI/ICC A117.1-2009 and to dispense a maximum of 0.25 gallons per metering cycle. [Initial comment: Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson.]
3. Provide tempered water for the lavatories using approved devices conforming to ASSE 1070 (the mixing valve furnished with the specified faucet does not appear to comply with ASSE 1070). Reference: Sections 416.5 and 607.1.2, IPC 2012.
06/01/2015 ROBERT SHERRY WATER REVIEW Completed
06/01/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
06/02/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following discrepancy.
The change to add a timeclock ( Keynote #7 ) Plan Sheet E2.0 to the restroom exhaust fans does not correspond with the restroom exhaust fan control detail #1 on Plan Sheet E0.0.
Ref: IBC sec.107.2.1, NEC art.430.
06/09/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/18/2015 KROBLES1 OUT TO CUSTOMER Completed