Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T15CM02297
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/01/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. No information has been submitted to show that the installation of the vacuum relief valve for the water heater on the hot water supply pipe complies with the manufacturer's listing requirements. [Initial comment: Provide information to show that the installation of the vacuum relief valve for the water heater on the hot water supply pipe complies with the manufacturer's listing requirements. Reference: Section 303.2, IPC 2012.] 2. Revise the specification of the automatic faucet to require the cycle time to be adjusted to a minimum of ten seconds per Section 606.4, ANSI/ICC A117.1-2009 and to dispense a maximum of 0.25 gallons per metering cycle. [Initial comment: Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson.] 3. Provide tempered water for the lavatories using approved devices conforming to ASSE 1070 (the mixing valve furnished with the specified faucet does not appear to comply with ASSE 1070). Reference: Sections 416.5 and 607.1.2, IPC 2012. |
06/01/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
06/01/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
06/02/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following discrepancy. The change to add a timeclock ( Keynote #7 ) Plan Sheet E2.0 to the restroom exhaust fans does not correspond with the restroom exhaust fan control detail #1 on Plan Sheet E0.0. Ref: IBC sec.107.2.1, NEC art.430. |
06/09/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
06/18/2015 | KROBLES1 | OUT TO CUSTOMER | Completed |