Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T15CM02297
Parcel: 10512020C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM02297
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2015 DAVID RIVERA ZONING REVIEW Approved
04/08/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide ventilation for the corridors. Reference: Section 401.2, IMC 2012.
2. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2012.
04/08/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
04/08/2015 ROBERT SHERRY WATER REVIEW Reqs Change 1. Provide the size and serial number of the water meter and the size of the backflow preventer serving this building.
2. Provide the total demand served by the water meter.
04/08/2015 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change 1. Provide structural calculations for all structural revisions shown on structural sheets.
2. Provide structural details and calculations for the wall mounted water heater.
END OF REVIEW
04/08/2015 JASON GREEN ENGINEERING REVIEW Approved
04/08/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide information to show that the installation of the vacuum relief valve for the water heater on the hot water supply pipe complies with the manufacturer's listing requirements. Reference: Section 303.2, IPC 2012.
2. Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson.
04/08/2015 KEN BROUILLETTE FIRE REVIEW Approved
04/08/2015 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/06/2015 KROBLES1 WWM REVIEW Needs Review