Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T15CM02281
Parcel: 117062000

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T15CM02281
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/03/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. GENERAL: THE REVISION LETTER DATED OCTOBER 26, 2015, INDICATES THE FOUNDATION WAS REDESIGNED TO ACCOMODATE THE TOWER CRANE, WHICH IMPACTS ALL THE CONCRETE SLABS ABOVE. NO NEW CALCULATIONS WERE SUBMITTED FOR THIS REDESIGN. PLEASE VERIFY.
11/09/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Coordinate the proposed locations of the grease interceptor and the backflow preventers. They appear to be in different locations on sheets P1.1 and X1. Reference: Section 107.2.1, IBC 2012.
11/16/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/23/2015 KROBLES1 OUT TO CUSTOMER Completed