Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T15CM02281
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/03/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. GENERAL: THE REVISION LETTER DATED OCTOBER 26, 2015, INDICATES THE FOUNDATION WAS REDESIGNED TO ACCOMODATE THE TOWER CRANE, WHICH IMPACTS ALL THE CONCRETE SLABS ABOVE. NO NEW CALCULATIONS WERE SUBMITTED FOR THIS REDESIGN. PLEASE VERIFY. |
11/09/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Coordinate the proposed locations of the grease interceptor and the backflow preventers. They appear to be in different locations on sheets P1.1 and X1. Reference: Section 107.2.1, IBC 2012. |
11/16/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/23/2015 | KROBLES1 | OUT TO CUSTOMER | Completed |