05/28/2015 STEVE SHIELDS ZONING REVIEW Approved
06/02/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/02/2015 ROBERT SHERRY WATER REVIEW Completed
06/05/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PREVIOUS COMMENT 4: THE NORTH ARROW WAS NOT ADDED TO ALL THE PLANS AS REQUESTED. PLEASE PROVIDE.
2. PREVIOUS COMMENT 7: KEYNOTE 6 ON SHEET S2.0 HAS NOT BEEN REMOVED. PLEASE REVISE.
3. PREVIOUS COMMENT 8: NOTE 12 ON SHEET S2.0 INDICATES #5 AT 24" OC, WHILE NOTE 2 ON SHEET S2.1 INDICATES #4 AT 24" OC. PLEASE COORDINATE.
06/08/2015 FDILLON1 DRB REVIEW Approved Architectural Site Plan matches previously approved DRB site plan. Project will require Design Professional review at the time elevations are submitted. FD