05/14/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following discrepancy.
General note #28, is in conflict with notes on plan sheets 'M1', 'L-1A', for conduit depths and also plan sheets 'PV1E-2F', 'E3F', and 'PV2E-2F', "E-3F'.