Permit Number: T15CM02107
Parcel: 13013050A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM02107
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/01/2015 MARTIN BROWN FIRE REVIEW Approved
04/10/2015 SPOWELL1 ZONING REVIEW Needs Review
04/10/2015 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
04/10/2015 SHANAE POWELL COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review Change of use is an impact fee push
04/10/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/10/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please indicate conductor types and sizes for riser conductors at service, also verify that 3 sets of 350KCMIL is sized correctly for total load .Plan sheet E3.
Ref: NEC 110.3, 310.15. IBC 107.2.1
04/10/2015 SPOWELL1 ENGINEERING REVIEW Needs Review
04/10/2015 ROBERT SHERRY WATER REVIEW Approved
04/10/2015 GERRY KOZIOL WWM REVIEW Passed
04/10/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed