Review Date Reviewer's Name Type of Review Description Status Comments
04/22/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
04/23/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Identify which of the two 30-gallon water heaters is to be installed and place the specifications (e.g. manufacturer, model, capacity, BTUH input, and etc.) for the proposed water heater on the drawings. [Initial comment: Provide the specifications and listing information for the proposed water heater. Reference: Sections 303.2 and 501.5, IPC 2012 and Section 107.2.1, IBC 2012.]
2. Include the expansion tank on the detail. [Initial comment: Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, vacuum relief or other anti-siphon device, safety pan, and valves. Reference: Sections 503, 504, 606.1, and 607.3, IPC 2012.]
3. Provide a route for the water heater flue that does not pass through an HVAC plenum and show it on the drawing. [Initial comment: Verify that the new flue does not pass through an HVAC plenum. Reference: Section 601.4, IMC 2012.]

Final Status

Task End Date Reviewer's Name Type of Review Description
05/13/2015 AROMERO4 OUT TO CUSTOMER Completed