Review Date Reviewer's Name Type of Review Description Status Comments
05/06/2015 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T15CM01946 R1
These comments apply to the Suntrac Solar Air & Heat system only. The 14 panel PV system was approved 03/27/2015.

PLAN REVIEW COMMENTS
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code, 2012 International Fire Code, 2011 National Electrical Code and Arizona Revised Statutes. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL NOTES:

1. Provide ΒΌ" = 1' scaled drawings with legible notation (minimum 3/32" lettering).
2. Provide a system layout plan showing the location of system components in relation to both structures and mechanical components.
3. Provide a line diagram identifying each component and installation details. Include fluid types and applied pressures.

STRUCTURAL PLANS:

1. The roof structure may not be suitable for additional dead loading without modification. Show structural sizes along with spans and any other load bearing information for determining the roof load carrying capacity, R301.1 & Table R802.5.1.
2. Demonstrate the ability for supporting the existing and additional dead load along with a 20 PSF live load; show point loads applied to each truss, M1401.
3. Provide load calculations, R301.1. Show the size and total number and spacing of lag bolts, R301.1.
4. Provide sufficient standoffs for achieving a point load calculation under 45 pounds, R301.1.
NOTES / SPECIFICATIONS

1. Show all equipment listings by an Independent Testing Agency for safety standards, M1301.5. The J&J Engineering report does not address safety standards.