Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T15CM01946
Parcel: 133471140

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T15CM01946
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/03/2015 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T15CM01946 R1 Suntrac Solar Air & Heat
PLAN REVIEW COMMENTS
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code, 2012 International Fire Code, 2011 National Electrical Code and Arizona Revised Statutes. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL NOTES:

1. Provide ΒΌ" = 1' scaled drawings with legible notation (minimum 3/32" lettering).
2. Provide a system layout plan showing the location of system components in relation to both structures and mechanical components.
3. Provide a line diagram identifying each component and installation details. Include fluid types and applied pressures.

STRUCTURAL PLANS:

1. The roof structure may not be suitable for additional dead loading without modification. Show structural sizes along with spans and any other load bearing information for determining the roof load carrying capacity, R301.1 & Table R802.5.1.
2. Demonstrate the ability for supporting the existing and additional dead load along with a 20 PSF live load; show point loads applied to each truss, M1401.
3. Provide load calculations, R301.1. Show the size and total number and spacing of lag bolts, R301.1.
4. Provide sufficient standoffs for achieving a point load calculation under 45 pounds, R301.1.
NOTES / SPECIFICATIONS

1. Show all equipment listings by an Independent Testing Agency for safety standards, M1301.5.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/07/2015 AROMERO4 APPROVAL SHELF Completed
04/07/2015 AROMERO4 OUT TO CUSTOMER Completed
04/07/2015 AROMERO4 REJECT SHELF Completed