Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T15CM01938
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/01/2015 | MARTIN BROWN | FIRE | REVIEW | Approved | |
04/06/2015 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
04/10/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
04/10/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the energy code analysis for the building envelope, coordinating the building components used in the analysis with those shown on the drawing (e.g. the roof does not show continuous insulation in the sections on sheetA5.0). Reference: Section C303.1, IECC 2012, as amended by the City of Tucson. 2. The intent of the energy conservation code is to address the entire building (i.e. envelope, mechanical, and lighting). The shell construction does not include mechanical or lighting construction so the individual tenant improvements will have to submit a complete COMcheck analysis using the code that is current when they apply for a permit. Reference: Section C101.4.5, IECC 2012. |
04/13/2015 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: 6351 E. Broadway Blvd. T15CM01938 Building Plan (1st Review) TRANSMITTAL DATE: April 13, 2015 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. The building plans cannot be approved until the revision to development package, DP1-0143, has been approved. 3. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
04/13/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The rim elevation of the next upstream sanitary manhole (2578.76') is less than 12" below the first floor elevation (2579.48'). Provide a backwater valve per Section 715.1, IPC 2012, as amended by the City of Tucson. |
04/15/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/21/2015 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |