Permit Number: T15CM01922
Parcel: 123070530

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T15CM01922
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/31/2015 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T15CM01922
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

SECTIONS - DETAILS:

1. Clarify the placement of ceiling/roof insulation for determining the need for attic ventilation, R806. Update detail #1 & 2, sheet 5.
2. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing (closed cell spray tight to the roof sheathing or rigid board sealed to roof framing), R806.5. This condensation control provision is necessary for code compliance and may be layered with batt insulation for achieving the total required roof R-value.

ELECTRICAL PLANS:

1. Show locations of each smoke alarm, R314. Smoke alarms are also required outside each separate sleeping area, R314.3.2. Show a smoke alarm on each side of the bedroom doors in the immediate vicinity.
2. Interior alterations require the installation of smoke alarms at existing bedrooms, R314.3.1. Provide notation if existing or proposed.
3. Show or notate the requirement for a carbon monoxide detector outside of bedroom doors, when the dwelling includes an attached garage or gas appliance, R315.
4. Protect all new and extended interior 15A & 20A proposed outlets (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors with combination type arc-fault circuit interrupters, E3902.12.
5. Provide notation requiring tamper resistant receptacles for 125 volt, 15A and 20A receptacles, R4002.14.

OUTDOOR LIGHTING CODE

1. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations. Unidentified fixtures are assumed to be unshielded (non-FCO style).

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
09/09/2015 KEN BROUILLETTE FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/15/2015 AROMERO4 OUT TO CUSTOMER Completed