Permit Number: T15CM01909
Parcel: 127022570

Address:
5201 E 2ND ST

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T15CM01909
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/24/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Needs Review
03/24/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide thermal load and HVAC equipment-sizing calculations to confirm the specified heat pumps for each apartment. Reference: Section R403.6, IECC 2012.