Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM01901
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/23/2015 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 03/23/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 03/23/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/23/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 03/23/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A-2; FLOOR PLAN: THE CITY OF TUCSON REQUIRES ALL LETTERING TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE SECTION CUTS VERBIAGE. 2. SHEET A-2; FLOOR PLAN: PLEASE REVISE THE MOP SINK KEYNOTE ON THE PLAN. 3. SHEET A-2; PROVIDE A DETAIL FOR THE SUPPORT OF THE NEW WATER HEATER. INCLUDE STRUCTURAL CALCULATIONS AS REQUIRED. 4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 03/23/2015 | RSHERRY1 | WWM | REVIEW | Passed | No water meter size change. |
| 03/23/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Revisew the drains for the 3-compartment sink to provide 3 independent indirect drains. 2. Coordinate the model nuber of the specified backflow preventer for the beverage fountain and the froster with the applicable ASSE standard. (Watts model 009 backflow preventers are listed to ASSE 1013, not ASSE 1022.) |
| 03/23/2015 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 03/23/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/26/2015 | AROMERO4 | FIRE | REVIEW | Needs Review |