Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM01850
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/19/2015 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 03/19/2015 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 03/20/2015 | ERIC NEWCOMB | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
| 03/20/2015 | ERIC NEWCOMB | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 03/20/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET T1.1; SUMMARY OF GOVERNING REGULATIONS: PLEASE REVISE THE EDITION OF THE VARIOUS BUILDING CODES. 2. SHEET T1.1; SUMMARY OF GOVERNING REGULATIONS: PLEASE REVISE THE WEBSITE ADDRESS FROM MARANA TO TUCSON. 3. SHEET T1.1; FIRE PROTECTION NOTES: ARE THESE NOTES PERTINENT TO THIS PROJECT? PLEASE VERIFY. 4. STRUCTURAL CALCULATIONS; SHEET #1: WHAT PUBLICATION IS THE REFERENCE MADE TO FOR THE MINIMUM WIND LOADS? PLEASE VERIFY AND ADD TO THE CALCULATIONS. 5. SHEET A1.1; SECTION 4: ALL DETAIL REFERENCES ON THIS SECTION ARE INCORRECT. PLEASE REVISE. |
| 03/20/2015 | ENEWCOM1 | WATER | REVIEW | Passed | |
| 03/20/2015 | ERIC NEWCOMB | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 03/20/2015 | ENEWCOM1 | WWM | REVIEW | Passed | |
| 03/20/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/24/2015 | AROMERO4 | FIRE | REVIEW | Needs Review |