Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T15CM01847
Parcel: 116183320

Address:
450 N GRANDE AV

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T15CM01847
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/09/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please clarify or make corrections as necessary for a safe and code compliant electrical installation.
#1. Indicate the total number and sizes of conductors in conduit per keynote #7 on plan sheet E2.
#2. Include equipment ground conductor and size, type, in pole lighting circuit. Plan sheet E3.
#3. Be more specific on grounding detail #5, plan sheet E3.Indicate wire size, type, method of taps, (approved for direct burial) if underground. Also include the counterpoise ground conductor in the trench details if that's how its going to be installed, or provide additional information on site plan.
#4. Provide a detail for the pedestal feeder connections to the pedestals, include equipment and counterpoise ground terminations. Include wiring methods such as taps and or splices. This provides clarification for the contractor and the inspector.
Ref: IBC sec. 107.2.1, NEC art. 110.3, 250, 300, 551.