Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T15CM01844
Parcel: 12112043B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM01844
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/03/2015 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change SHEET A1.1
1. Provide details for water heater support and structural calculations.
SHEET A1.2
2. Delete all references to ADA
3. Correct all details shown to comply with the 2012 IBC, Chapter 11 and the 2009 Edition of ICC A117.1.
4. Detail 3 is a generic detail of the toilet rooms and is not acceptable. Please provide all accessible code requirements on Detail 6 including but not limited to dimensions, clearances, accessories, mounting heights and signage.
END OF REVIEW
04/10/2015 ROBERT SHERRY WATER REVIEW Reqs Change Tucson Water limits a 5/8" meter to a maximum demand of 15 GPM. Provide a letter from Tucson Water confirming that the use of a 5/8" water meter will be allowed for this project.
04/10/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change If the proposed shower does not have a pre-fabricated receptor, provide details to show that the construction of the receptor complies with the requirements of Section 417.5.2, IPC 2012.
04/10/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide full compliance with IECC for interior Lighting and Tucson Outdoor Lighting Code.
04/10/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Demonstrate energy code compliance for the alterations to the building envelope (e.g. new storefront) based on the current code. Reference: Sections C101.4.3, C101.5, and C103.2, International Energy Conservation Code 2012.
2. Provide NFRC fenestration product ratings for the U-factor and the SHGC values on COMcheck or use the appropriate default U-factor and SHGC values from Tables C303.1.3 (1), C303.1.3 (2) and C303.1.3.(3), IECC 2012. Factory-manufactured windows are required to have certificates attesting to their compliance to NFRC Standards 100 and 200 and can be provided by the manufacturer or found at www.nfrc.org. For site assembled commercial products, the NFRC component modeling approach program enables commercial window manufacturers to produce bid reports to prove energy performance prior to being awarded a job and provide finalized label certificates once the product has been installed. Fenestration performance reports based on AAMA 507 are based on energy simulations only (no actual testing) and are not acceptable. Reference: Section C303.1.3, IECC 2012.
3. Provide structural details to show how the fan coil units are to be connected to the building structure. Reference: Section 302.1, IMC 2012.
4. Revise the plans as required to provide a separation of at least ten feet between the air intake opening for fan coils FC-5 and FC-6 and the lot line. Reference: 401.4 (1), IMC 2012.
5. Show the size, route, and termination of the dryer exhaust duct. Reference: Sections 504.1, 504.2, 504.4 and, 504.6, IMC 2012.
6. Show how unauthorized access to the refrigerant circuit access ports of the condensing units is to be prevented. Reference: Section 1101.10, IMC 2012.