Permit Number: T15CM01843
Parcel: 116150790

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM01843
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/19/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/19/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
03/19/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revise the water fixture units to use the values for public fixtures.
2. Clarify how the fixture drain from the new service sink is to be connected to the existing building drain.
03/19/2015 ROBERT SHERRY WATER REVIEW Reqs Change The proposed total water demand served by the existing 5/8" water meter is over 20 GPM. Provide a water meter at least 3/4" in size.
03/19/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/23/2015 AROMERO4 WWM REVIEW Completed
03/23/2015 AROMERO4 ELECTRICAL-COMMERCIAL REVIEW Needs Review
03/23/2015 JASON GREEN ENGINEERING REVIEW Approved
03/23/2015 MICHAEL ST. PAUL ZONING REVIEW Approved
03/23/2015 AROMERO4 FIRE REVIEW Needs Review