Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM01840
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/19/2015 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 03/19/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 03/19/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Revise the water fixture units to use the values for public fixtures. |
| 03/19/2015 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | The proposed total water demand served by the existing 5/8" water meter is over 20 GPM. Provide a water meter at least 3/4" in size. |
| 03/19/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A2: THE CORRIDOR LEADING TO THE ACCESSIBLE RESTROOM CAN NOT PASS THROUGH AN INTERVENING SPACE PER THE IBC SECTION 1018.6. PLEASE REVISE. 2. SHEET A4: PLEASE REVISE THE WATER HEATER SUPPORT PLATFORM TO PLYWOOD. 3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 03/19/2015 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 03/19/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/23/2015 | AROMERO4 | WWM | REVIEW | Completed | |
| 03/23/2015 | AROMERO4 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 03/23/2015 | AROMERO4 | FIRE | REVIEW | Needs Review |