Permit Number: T15CM01701
Parcel: 124150070

Address:
802 E 16TH ST

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T15CM01701
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/13/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Explain the note on detail 3/M1.1, that says: "90 DEG PER REVOLUTION"
2. Provide the sequence of operation for the duct stat.
03/13/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Revise the design of the sediment trap shown in detail 1/P1.1 to comply with the requirements of Section 408.4, IFGC 2012.