Permit Review Detail
Review Status: Completed
Review Details: WALK THRU - COMM
Permit Number - T15CM01701
Review Name: WALK THRU - COMM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/13/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Explain the note on detail 3/M1.1, that says: "90 DEG PER REVOLUTION" 2. Provide the sequence of operation for the duct stat. |
| 03/13/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Revise the design of the sediment trap shown in detail 1/P1.1 to comply with the requirements of Section 408.4, IFGC 2012. |