Permit Number: T15CM01698
Parcel: 14041867A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T15CM01698
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/16/2015 KEN BROUILLETTE FIRE REVIEW Reqs Change PLEASE INDICATE COMPLIANCE WITH IFC SECTION 3209 ON PLANS
03/26/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. GENERAL: WHERE ON THE DRAWINGS ARE THE 4X4X ¼ STEEL TUBE COLUMNS (PAGE 17 OF THE CALCULATIONS) AND THE 2 ½ X 2 ½ X ¼ COLUMN KNEE BRACES (PAGE 28 OF THE CALCULATIONS) INDICATED? SEVERAL SECTIONS ON THE DRAWINGS INDICATE TS 4X4X 3/16 COLUMNS, BUT THE KNEE BRACE SIZES AND CONNECTIONS WERE NOT LOCATED. PLEASE VERIFY.
2. GENERAL: THE GENERAL NOTES ON SHEET M-IND-1 INDICATE TO SEE ME-01, 01A, 01B, 01C, AND 01D FOR SUPPORTING AND OTHER INSTALLATION DETAILS. WHERE ARE THESE SHEETS LOCATED? PLEASE VERIFY.
3. GENERAL: WHERE ON THE DRAWINGS IS THE 5X3X ¼ ANGLE AND BOLTS AT THE BEAM CONNECTIONS (PAGE 29 OF THE CALCULATIONS) INDICATED? PLEASE VERIFY.
4. GENERAL: WHERE ON THE DRAWINGS IS THE COLUMN BASE PLATE AND ANCHORS (PAGE 31 OF THE CALCULATIONS) INDICATED? PLEASE VERIFY.
5. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
04/02/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
04/02/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/03/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please clarify or indicate the following on plan sheets 401 , 402.
(a). Conduit, conductor sizes and types, circuiting, homeruns, load calc's, fixture schedule for all conveyor lighting, ceiling fans.
(b). Full compliance with IECC for lighting.
(c). Be advised, all other equipment and installations indicated as, "by others" on the plans will require permits and inspections if not existing.
Ref: IBC sec.107.2.1, Nec art. 408.4, 110.3
04/08/2015 MICHAEL ST. PAUL ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/17/2015 FERNE RODRIGUEZ OUT TO CUSTOMER Completed