Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM01635
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/11/2015 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
03/11/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
03/11/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | #1.Provide complete panel schedules,include buss and main breaker amp ratiing. #2. Provide home run circuiting for all lighting and for tankless water heater, reflect on panel schedules. |
03/11/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
03/11/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
03/11/2015 | RSHERRY1 | WWM | REVIEW | Passed | No water meter size change. |
03/11/2015 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
03/11/2015 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
03/11/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
03/13/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed |