Review Date Reviewer's Name Type of Review Description Status Comments
06/05/2015 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T15CM01622
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

FLOOR PLANS:

1. Show compliance with R310 providing egress from the master bedroom by meeting the following minimum specifications. (30x30 is undersized if not casement style)
a. Maximum sill height of 44".
b. Minimum net clear opening area of 5.7 SQ FT (5 SQ FT 1st floor).
c. Minimum net clear opening dimension of 24" height and 20" width.

STRUCTURAL PLANS:

1. Show a framing plan and section for the metal porch structure shown as building #8 on the Site Plan, R106.1.1.
2. Show a framing plan and section for the 5'-8" x 5'-3" if this structure is attached to the dwelling, R106.1.1. This storage building does not require a permit and plans if free standing; clarify.

SECTIONS - DETAILS:

1. Provide consistent building references, R106.1.1. Update Patio Porch to #4 on sheet #13 as shown on the approved Site Plan.
2. Show one-hour fire-resistive framed construction in compliance with IBC Table 720.1(2). Update the wall section on sheet #13 showing 7/8" stucco rather than ½" and add "type X" to the 5/8" gypsum board note.

MECHANICAL PLANS:

1. Show dryer vent size and location for venting to exterior, M1501.

ELECTRICAL PLANS:

1. Interior alterations require the installation of smoke alarms at existing bedrooms, R314.3.1. Provide notation if existing or proposed.
2. Clarify the electrical box in the laundry room; sheet #3 shows a junction box and sheet #8 shows a sub panel. A panelboard or disconnect box requires a clear working space of 30"wide x 36"deep, E3405.2. The washer may be placed in front of a junction box.
3. Show one 20 AMP branch circuit in the laundry area; this circuit may not serve other locations, E3703.3 and 3901.8.
4. Protect all interior 15A & 20A proposed outlets (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors with combination type arc-fault circuit interrupters, E3902.12.

OUTDOOR LIGHTING CODE

1. Show the outdoor fixtures as full cut-off FCO style, or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits. Adjustable security light fixtures are unshielded, not FCO.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review