Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T15CM01606
Parcel: 13734001A

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T15CM01606
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/16/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide the specifications for the water heater, WH-2, shown on the plumbing plans. Reference: Section 107.2.1, IBC 2012.
2. Provide a design for the mounting shelf for water heater WH-2, along with structural calculations to show that the water heater is safely supported. Reference: Section 301.2, IPC 2012.
03/16/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide calculations to show how ventilation will be provided for Classroom 7 (HP-1). Reference: Section 401.2, IMC 2012.
03/16/2015 ROBERT SHERRY WATER REVIEW Reqs Change Provide the size and serial number of the existing water meter along with the total demand being served by the meter. Provide the size of the existing (?) backflow preventer. Reference: Section 107.2.1, IBC 2012.
03/17/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/19/2015 SHANAE POWELL OUT TO CUSTOMER Completed
03/19/2015 CPIERCE1 REJECT SHELF Completed