Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T15CM01606
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/16/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide the specifications for the water heater, WH-2, shown on the plumbing plans. Reference: Section 107.2.1, IBC 2012. 2. Provide a design for the mounting shelf for water heater WH-2, along with structural calculations to show that the water heater is safely supported. Reference: Section 301.2, IPC 2012. |
03/16/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide calculations to show how ventilation will be provided for Classroom 7 (HP-1). Reference: Section 401.2, IMC 2012. |
03/16/2015 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Provide the size and serial number of the existing water meter along with the total demand being served by the meter. Provide the size of the existing (?) backflow preventer. Reference: Section 107.2.1, IBC 2012. |
03/17/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/19/2015 | SHANAE POWELL | OUT TO CUSTOMER | Completed |
03/19/2015 | CPIERCE1 | REJECT SHELF | Completed |