Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM01551
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/09/2015 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 03/09/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the font size used on the drawings (e.g. M3) to a minimum height of 3/32-inch. Reference: Section 107.2.1, IBC 2012. 2. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted (i.e. exhaust shall operate even when the lights are off) during occupied hours. Reference: Section 403.2.1 (4), IMC 2012. |
| 03/09/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide the following information. (a). Grounding detail for new service equipment. (b). Detail for tap into existing landlord wireway for SES. (a). Complete fault current analysis. |
| 03/09/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 03/09/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/09/2015 | RSHERRY1 | WWM | REVIEW | Passed | No water meter size change. |
| 03/09/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson. 2. Approved devices conforming to ASSE 1070 are required to provide tempered water for the lavatories in restrooms. Reference: Sections 416.5 and 607.1.2, IPC 2012. |
| 03/09/2015 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 03/09/2015 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 03/09/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |