Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM01505
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/05/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
03/05/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
03/06/2015 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
03/06/2015 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
03/09/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide energy code compliance calculations for the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C101.4.5, C103.2, and C401.2, International Energy Conservation Code 2012. 2. Provide NFRC fenestration product ratings for the U-factor and the SHGC values on COMcheck or use the appropriate default U-factor and SHGC values from Tables C303.1.3 (1), C303.1.3 (2) and C303.1.3.(3), IECC 2012. Reference: Section C303.1.3, IECC 2012. |
03/09/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
03/09/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
03/09/2015 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
03/09/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
05/13/2015 | AROMERO4 | WWM | REVIEW | Completed |