Permit Number: T15CM01487
Parcel: 13323099K

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T15CM01487
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/01/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
04/01/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Demonstrate energy code compliance for the alterations to the building envelope based on the current code. Reference: Sections C101.4.3, C101.5, and C103.2, International Energy Conservation Code 2012.
2. Provide NFRC fenestration (i.e. doors and windows) product ratings for the U-factor and the SHGC values on COMcheck or use the appropriate default U-factor and SHGC values from Tables C303.1.3 (1), C303.1.3 (2) and C303.1.3.(3), IECC 2012. Reference: Section C303.1.3, IECC 2012.
04/06/2015 SPOWELL1 BUILDING-COMMERCIAL REVIEW Needs Review