Permit Number: T15CM01394
Parcel: 10602265B

Address:
320 W PRINCE RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM01394
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/01/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Secondary drainage has not been provided. [Initial comment: Provide secondary (overflow) roof drainage. Reference: Sections 1101, 1106 and 1108, IPC 2012, and Sections 1611.1 and 1611.3, IBC 2012.]
05/01/2015 ROBERT SHERRY WATER REVIEW Completed
05/01/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The components described in COMcheck show continuous insulation for both the roof and the walls - where is this shown on the drawings? [Initial comment: Provide energy code compliance calculations for the additions to the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the additions to the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C101.4.3, C101.5, and C103.2, International Energy Conservation Code 2012.]
2. The data for the glazing appears to be for only the glass, not for the glass plus the frame. Provide the NFRC-certified values (try www.nfrc.org ). Data is also needed for the door also. [Initial comment: Provide NFRC fenestration product ratings for the U-factor and the SHGC values on COMcheck or use the appropriate default U-factor and SHGC values from Tables C303.1.3 (1), C303.1.3 (2) and C303.1.3.(3), IECC 2012. Reference: Section C303.1.3, IECC 2012.]