| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/06/2015 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/10/2015 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/10/2015 | RONALD BROWN | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
| 04/16/2015 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 04/17/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 04/20/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide energy code compliance calculations for the additions to the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the additions to the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C101.4.3, C101.5, and C103.2, International Energy Conservation Code 2012. 2. Provide NFRC fenestration product ratings for the U-factor and the SHGC values on COMcheck or use the appropriate default U-factor and SHGC values from Tables C303.1.3 (1), C303.1.3 (2) and C303.1.3.(3), IECC 2012. Reference: Section C303.1.3, IECC 2012. 3. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012. |
| 04/20/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference: Section 301.2, IPC 2012. 2. Provide secondary (overflow) roof drainage. Reference: Sections 1101, 1106 and 1108, IPC 2012, and Sections 1611.1 and 1611.3, IBC 2012. |
| 04/20/2015 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | The water calculations appear to indicate that a new 2" water meter is to be installed along with a new 3" reduced pressure backflow prevention assembly to accommodate a demand of only 59 GPM. If this is correct, what is the size of the existing water meter? If the existing water meter is to be retained, provide the meter size and serial number. |
| 04/27/2015 | AROMERO4 | WWM | REVIEW | Completed | |
| 04/29/2015 | LOREN MAKUS | ENGINEERING | REVIEW | Approved |