Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Permit Number - T15CM01378
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/07/2015 | STEVE SHIELDS | ZONING | REVIEW | Needs Review | P&DS TRANSMITTAL FROM: Steve Shields, Lead Planner PROJECT: T14CM01378 344 W. 44th Street Bedroom, livingroom and porch addition. TRANSMITTAL: April 7, 2015 COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1). This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10. The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A). Based on a wall height of 9'-8" the required perimeter yard setback to the west property line is 6'-5", proposed perimeter yard to the west property lines is 5'-0". The minimum setback to the front street perimeter property line is the greater of twenty (20) feet, or one and one-half (1 ½) the height of the proposed wall (UDC 6.4.5.C.1.a). Based on a wall height of 12'-4" the required front street perimeter yard is 20'-0", proposed front street perimeter yard is 8'-0". |
| 04/07/2015 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 04/07/2015 | SSHIELD1 | NPPO | REVIEW | Passed | |
| 07/13/2015 | AROMERO4 | BUILDING-RESIDENTIAL | REVIEW | Needs Review |