Permit Number: T15CM01362
Parcel: 11918029L

Address:
1340 W AJO WY

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T15CM01362
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/28/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Comment not addressed; re-read the second comment. [Third comment: A note requiring the contractor to comply with the applicable code sections is insufficient; provide a note that states which features the controls shall have in order to comply with the code requirements (e.g. re-read the second comment).] [Second comment: Show that the proposed HVAC system meets the control requirements of Section C403.2.4: set-point overlap restriction, automatic set-back and shut-down controls, automatic start capabilities, and shutoff damper controls. Reference: Section C303.1, International Energy Conservation Code 2012.] [Initial comment: Show that the proposed HVAC system meets the minimum efficiency, operational, and control requirements of Sections C403.2, C403.3 and, if neither the efficient lighting system nor the on-site renewable energy options are selected, C406.2, IECC 2012 (e.g. provide the mechanical energy code compliance certification from COMcheck). Reference: Section C303.1, International Energy Conservation Code 2012.]