Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T15CM01362
Parcel: 11918029L

Address:
1340 W AJO WY

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T15CM01362
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/21/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/22/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change A note requiring the contractor to comply with the applicable code sections is insufficient; provide a note that states which features the controls shall have in order to comply with the code requirements (e.g. re-read the second comment). [Second comment: Show that the proposed HVAC system meets the control requirements of Section C403.2.4: set-point overlap restriction, automatic set-back and shut-down controls, automatic start capabilities, and shutoff damper controls. Reference: Section C303.1, International Energy Conservation Code 2012.] [Initial comment: Show that the proposed HVAC system meets the minimum efficiency, operational, and control requirements of Sections C403.2, C403.3 and, if neither the efficient lighting system nor the on-site renewable energy options are selected, C406.2, IECC 2012 (e.g. provide the mechanical energy code compliance certification from COMcheck). Reference: Section C303.1, International Energy Conservation Code 2012.]
05/22/2015 STEVE SHIELDS ZONING REVIEW Approved
05/22/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed