Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T15CM01362
Parcel: 11918029L

Address:
1340 W AJO WY

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T15CM01362
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/19/2015 KEN BROUILLETTE FIRE REVIEW Approved
03/20/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET T1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE CLOSED SPECIFICATION PROVIDERS.
2. SHEET T1; PROJECT INFORMATION: PROVIDE ON THE DRAWINGS THE MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES PER THE IBC TABLE 2902.1.
3. SHEET A1 (FLOOR PLAN); SHEET A4.1 (SECTION 2): SECTION 2/A4.1 IS CUT AT AN ENDWALL ON THE PLAN, WHILE THE SECTION INDICATES A SIDEWALL WITH THE METAL BUILDING FRAME. PLEASE CLARIFY.
4. SHEET A1; FLOOR PLAN: PLEASE INDICATE A NORTH ARROW ON THE PLAN.
5. SHEET A1; FLOOR PLAN: PLEASE INDICATE WALL ELEVATION 2/A2 ON THE PLAN.
6. SHEET A1 (FLOOR PLAN); SHEET A4.1 (SECTION 1): SECTION 1/A4.1 IS CUT AT AN ENDWALL, WHILE THE SECTION INDICATES A SIDEWALL WITH THE METAL BUILDING FRAME. PLEASE CLARIFY.
7. SHEET A2.1; ELEVATIONS: PLEASE ADD A NOTE TO THIS SHEET TO REFERENCE SHEET A2 FOR THE EXTERIOR FINISH SCHEDULES.
8. SHEET A4; SECTIONS 1, 2, AND 3: PLEASE REVISE THE GRIDS ON THE SECTIONS TO MATCH THE PLAN.
9. SHEET A4.1; SECTIONS 1 AND 2: PLEASE REVISE THE GRIDS ON THE SECTIONS TO MATCH THE PLAN.
10. SHEET A6: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE CASH WRAP.
11. SHEET S1.1; CONCRETE GENERAL NOTES: NOTE 17 INDICATES A SOIL REPORT WAS USED FOR THE FOUNDATION DESIGN. PLEASE PROVIDE THAT REPORT FOR REVIEW.
12. SHEET S1.1; DETAIL 5: PLEASE PROVIDE STRUCTURAL CALCULATIONS FOR THE PYLON SIGN FOUNDATION DESIGN.
13. SHEET S2.1; PLAN NOTES: NOTE 7 INDICATES TO REFERENCE DETAILS 1/S1.1 AND 2/S1.1. PLEASE REVISE THE DETAIL REFERENCES.
14. GENERAL: PROVIDE A SITE PLAN WITH THIS SUBMITTAL.
15. GENERAL: NO DESIGN CALCULATIONS WERE FOUND FOR THE BUILDING FOUNDATION. WILL THIS BE A DEFERRED SUBMITTAL ALONG WITH THE PRE-ENGINEERED BUILDING? PLEASE VERIFY.
16. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
03/24/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Coordinate the location of the backflow preventer protecting the municipal water distribution system with the civil drawings; a new reduced pressure backflow prevention assembly is shown at the property line on the site utility drawing. Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf
2. Provide a design for the mounting shelf for the water heater. Show clearly how the platform is to be constructed and attached to the building structure. Reference: Section 301.2, IPC 2012.
3. Install the proposed vacuum relief valve for the water heater (detail 2/P2) per the manufacturer's listing information, i.e. with no valves located between the vacuum relief valve and the water heater. Reference: Section 303.2, IPC 2012.
4. For the use of PEX tubing, provide a branch tube sizing chart showing the correct size of PEX tubing to be used as a substitute for the copper pipe shown on the drawings. Reference: Sections 303.2 and 604.3, IPC 2012.
5. Provide roof drainage and gutter size calculations based on the 100-year hourly rainfall rate for Tucson, 3" per hour. Reference: Sections 1106.1 and, 1106.6, IPC 2012.
03/25/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide energy code compliance calculations for the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope (e.g. revise the insulation note as required to agree with the insulation shown in the energy analysis, show the U-factor and SHGF for fenestration, etc.). Reference: Sections C103.2 and C401.2, International Energy Conservation Code 2012.
2. Provide NFRC fenestration product ratings for the U-factor and the SHGC values on COMcheck or use the appropriate default U-factor and SHGC values from Tables C303.1.3 (1), C303.1.3 (2) and C303.1.3.(3), IECC 2012. Reference: Section C303.1.3, IECC 2012. (Note: For site assembled commercial products, the NFRC component modeling approach program enables commercial window manufacturers to produce bid reports to prove energy performance prior to being awarded a job and provide finalized label certificates once the product has been installed. Fenestration performance reports based on AAMA 507 are based on energy simulations only (no actual testing) and are not acceptable.)
3. Show how the "Additional Efficiency Package Requirements" noted in Section C406, IECC 2012 is to be addressed. Reference: Section C401.2, IECC 2012.
4. Show that the proposed HVAC system meets the minimum efficiency, operational, and control requirements of Sections C403.2, C403.3 and, if neither the efficient lighting system nor the on-site renewable energy options are selected, C406.2, IECC 2012 (e.g. provide the mechanical energy code compliance certification from COMcheck). Reference: Section C303.1, International Energy Conservation Code 2012.
5. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012.
6. Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted (i.e. the exhaust fans shall run continuously while the HVAC system supplies air into the restrooms). Reference: Section 403.2.1 (4), IMC 2012.
03/25/2015 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Family Dollar
T15CM01362
Building Plan (1st Review)

TRANSMITTAL DATE: March 25, 2015

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The building plans appear to meet the proposed development package but Zoning cannot approve until the development package, DP14-0192, has been approved.

3. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
03/25/2015 ROBERT SHERRY WATER REVIEW Completed
04/01/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide IECC compliance cert.
Please show full compliance with the Tucson Outdoor Lighting Code.
04/02/2015 ELIZABETH LEIBOLD ENGINEERING REVIEW Reqs Change Assure Dev Pkg DP14-0192 is approved before Engineering can approve bldg plans.