Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T15CM01295
Parcel: 11803402A

Address:
2115 W 33RD ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T15CM01295
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/10/2015 MICHAEL ST. PAUL ZONING REVIEW Approved
03/26/2015 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 3-26-15
Activity: T15CM01295
Address: 2115 W 33rd St
Applicant: David Baker

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Residential Code and local amendments. In order to facilitate a shorter back check time, we request that you provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions and concerns before permit approval.

STRUCTURAL / FRAMING PLAN:
1. Provide a minimum 48 inch braced wall panel next to the garage door or include provisions for an alternate braced wall panel as provided in section R602.10.6.
2. The maximum spacing between braced wall panels is 20 feet, R602.10.2.2.
3. Specify the sizes of all headers and beams, 801.2.
4. Provide a stamp from a registered design professional and lateral analysis for wood studs that exceed the prescriptive allowance of Table R602.3(5).

If you have any questions please contact:
Clayton Trevillyan, CBO
520.837.4913
Clayton.Trevillyan@tucsonaz.gov
Residential Plan Review