Permit Review Detail
Review Status: Completed
Review Details: WALK THRU - COMM
Permit Number - T15CM01245
Review Name: WALK THRU - COMM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/24/2015 | STEVE SHIELDS | ZONING | REVIEW | Passed | |
| 03/04/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | #1. Verify AIC at service pedestals per TEP. #2. Grounding Electrode System to terminate in load section of service equipment per NEC 250.24. ( page 10 ) |