Permit Number: T15CM01111
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM01111
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/24/2015 KEN BROUILLETTE FIRE REVIEW Approved
02/27/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A1.00; CODE SYNOPSIS: PLEASE REVISE THE NEC TO THE 2011 EDITION.
2. SHEET A1.15: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE FINISH AND DOOR SCHEDULE NOTES.
3. SHEET A1.30: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE NOTES.
4. SHEET A1.40; BARRICADE SECTIONS D AND F: A NOTE INDICATES TO SECURE THE 2X4 PLATE TO THE PLYWOOD FROM THE UNDERSIDE. PLEASE CLARIFY THIS. IT APPEARS THE PLYWOOD BUTTS INTO THE 2X4.
5. SHEET A1.40; PLAN B: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE NOTE AT THE INTERIOR CONCERNING REMOVING FURNISHINGS.
6. SHEET A1.40; PLANS A AND B: PLEASE PROVIDE A NORTH ARROW ON THESE PLANS.
7. SHEET A2.00; CONSTRUCTION PLAN: PLEASE PROVIDE A NORTH ARROW ON THIS PLAN.
8. SHEETS A2.00 AND A2.01; PLAN (INTERIOR PARTITIONS): THE INTERIOR PARTITION LEGEND INCLUDES A SOUND ATTENUATION WALL. IS THERE SUCH A WALL LOCATED ON THESE PLANS? PLEASE VERIFY.
9. SHEET A2.00; CODED NOTES: NOTES 8 AND 10 WERE NOT LOCATED ON THE PLAN. PLEASE VERIFY.
10. SHEET A2.00: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE CODED NOTES.
11. SHEET A2.01; CODED NOTES: NOTES 14, 16, AND 18 WERE NOT LOCATED ON THE PLAN. PLEASE VERIFY.
12. SHEET A2.01: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE CODED NOTES AND LEGEND.
13. SHEET A8.01: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE DETAILS B, C, AND D.
14. SHEET A8.40; SECTION A2: A NOTE ON THIS SECTION INDICATES TO REFER TO A2.00 FOR THE SHAPE OF THE MALL STRUCTURAL COLUMN. WHERE IS THIS LOCATED ON SHEET A2.00? PLEASE CLARIFY.
15. SHEET S2.00: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE CODED NOTES AND METAL STUD WALL SCHEDULE.
16. SHEET S2.00; FRAMING PLAN: PLEASE PROVIDE A NORTH ARROW ON THE PLAN.
17. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
03/09/2015 ROBERT SHERRY WATER REVIEW Completed
03/09/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
03/09/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
03/16/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change 3. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that in addition to signing the seal, the registrant shall include the date the document was sealed and that a notation shall be placed beneath the seal, written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).

Final Status

Task End Date Reviewer's Name Type of Review Description
03/23/2015 KROBLES1 OUT TO CUSTOMER Completed
03/23/2015 CPIERCE1 REJECT SHELF Completed