Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T15CM01100
Parcel: 110113730

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T15CM01100
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/17/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2012, for business occupancy (e.g. drinking fountain).
03/17/2015 ROBERT SHERRY WATER REVIEW Reqs Change 1. Section 604.1, IPC 2012 allows water distribution systems to be designed using accepted engineering methods. Provide the source of the method used to determine the water demand and size the water distribution system.
2. Tucson Water limits a 3/4" meter to a maximum demand of 22.5 GPM. Provide a letter from Tucson Water confirming that the use of a 3/4" water meter will be allowed for this project.
03/17/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide calculations demonstrating adequate ventilation using the current code. Reference: Section 403.2, IMC 2012.
03/19/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved