Permit Number: T15CM01100
Parcel: 110113730

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM01100
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/19/2015 STEVE SHIELDS ZONING REVIEW Approved
02/19/2015 LOREN MAKUS ENGINEERING REVIEW Approved
02/19/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
02/19/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET CS; CODE INFORMATION: THE OCCUPANCY TYPE IS LISTED AS MERCANTILE. PLEASE REVISE THE CLASSIFICATION PER THE IBC SECTION 304. VERIFY AND REVISE THE PLUMBING REQUIREMENTS AS NEEDED FOR THE REVISED CLASSIFICATION.
2. SHEET A201; ROOM FINISH SCHEDULE: PLEASE VERIFY THE REQUIREMENTS OF THE IBC SECTION 1210 ARE MET. IT DOES NOT APPEAR TO MEET THE WALL/PARTITION REQUIREMENTS.
3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
02/19/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/20/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change
02/20/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Explain the ultimate purpose of the ½" DCW drop described in keynote #5. Reference: Section 107.2.1, IBC 2012.
2. Clarify Keynote #15 - it refers to only the break room sink but it points to a lavatory, a mop sink, and a water closet.
3. Display the last line of the description, trim, and notes section for the electric water cooler in the plumbing fixture schedule.
02/20/2015 ROBERT SHERRY WATER REVIEW Reqs Change Provide the size of the water meter serving this suite, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2012.
02/20/2015 KEN BROUILLETTE FIRE REVIEW Approved
03/17/2015 AROMERO4 WWM REVIEW Completed