Permit Number: T15CM01098
Parcel: 140420200

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM01098
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/19/2015 STEVE SHIELDS ZONING REVIEW Approved
02/19/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012.
02/19/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
02/19/2015 ROBERT SHERRY WATER REVIEW Completed
02/19/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A1.0; FLOOR PLAN: THE PLAN INDICATES THERE IS NO NEW WORK IN THE EAST PORTION OF THE BUILDING. HOWEVER, WALL TYPE A (INDICATED AT NORTH, EAST, AND SOUTH WALLS) IS ADDING A NEW FURROUT STUD WALL. PLEASE CLARIFY.
2. SHEET A1.0; FLOOR PLAN (KEY NOTES): NOTE 1 INDICATES 'EXISTING-NO WORK THIS AREA'. THAT NOTE APPEARS ON THE SOUTH WALL (AT WINDOW E) AND THE NORTH OFFICE AREA (AT NEW WALL TYPE B). PLEASE CLARIFY.
3. SHEET S1.0; ROOF FRAMING PLAN: PLEASE CLEAR UP THE FRAMING KEYNOTE INDICATORS ON THE PLAN AND IN THE NOTES.
4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
02/19/2015 RSHERRY1 WWM REVIEW Passed No wastewater plumbing.
02/19/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
02/19/2015 LOREN MAKUS ENGINEERING REVIEW Approved
02/19/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/20/2015 KEN BROUILLETTE FIRE REVIEW Approved