Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM01098
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/19/2015 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
02/19/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012. |
02/19/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
02/19/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
02/19/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A1.0; FLOOR PLAN: THE PLAN INDICATES THERE IS NO NEW WORK IN THE EAST PORTION OF THE BUILDING. HOWEVER, WALL TYPE A (INDICATED AT NORTH, EAST, AND SOUTH WALLS) IS ADDING A NEW FURROUT STUD WALL. PLEASE CLARIFY. 2. SHEET A1.0; FLOOR PLAN (KEY NOTES): NOTE 1 INDICATES 'EXISTING-NO WORK THIS AREA'. THAT NOTE APPEARS ON THE SOUTH WALL (AT WINDOW E) AND THE NORTH OFFICE AREA (AT NEW WALL TYPE B). PLEASE CLARIFY. 3. SHEET S1.0; ROOF FRAMING PLAN: PLEASE CLEAR UP THE FRAMING KEYNOTE INDICATORS ON THE PLAN AND IN THE NOTES. 4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
02/19/2015 | RSHERRY1 | WWM | REVIEW | Passed | No wastewater plumbing. |
02/19/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
02/19/2015 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
02/19/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
02/20/2015 | KEN BROUILLETTE | FIRE | REVIEW | Approved |