Permit Number: T15CM01097
Parcel: 119421810

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM01097
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/19/2015 MICHAEL ST. PAUL ZONING REVIEW Approved
02/19/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
02/19/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify that the specified faucet for the two handwashing sinks in the lavatories is equipped with a mixing valve that complies with ASSE Standard 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
2. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012.
3. Clarify the reason for using an indirect waste connection for the soiled dish table sink. Reference: Section 802.1, IPC 2012.
02/19/2015 ROBERT SHERRY WATER REVIEW Reqs Change Provide the size of the existing water meter and provide the total demand served by the water meter.
02/19/2015 LOREN MAKUS ENGINEERING REVIEW Approved
02/20/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET G001; PROJECT RESPONSIBILITY MATRIX: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE.
2. SHEET G001; CODE ANALYSIS: PLEASE INDICATE ON THE DRAWING THAT THIS BUILDING HAS AUTOMATIC SPRINKLERS.
3. SHEET G003; LIFE SAFETY PLAN: THE PLAN INDICATES THE DIAGONAL DISTANCE OF THE AREA SERVED IS 119'-5". ANOTHER NOTE INDICATES THE REQUIRED SEPARATION BETWEEN EXITS IS 1/3 OF THE AREA SERVED = 35'-8". SHOULD THIS NUMBER BE 39'-8"? PLEASE VERIFY.
4. SHEETS D100 AND A100; ELEVATIONS: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE.
5. SHEET A600; INTERIOR FINISH SCHEDULE: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE.
6. SHEET A702; DETAIL 5: PLEASE PROVIDE THE BAR HEIGHT ON THE DETAIL.
7. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
02/20/2015 KEN BROUILLETTE FIRE REVIEW Approved
02/20/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/04/2015 AROMERO4 WWM REVIEW Completed
03/04/2015 AROMERO4 ELECTRICAL-COMMERCIAL REVIEW Needs Review