Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T15CM01084
Parcel: 13212113A

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T15CM01084
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/10/2015 KEN BROUILLETTE FIRE REVIEW Completed STATE FIRE MARSHAL APPROVAL REQUIRED
03/16/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A4; DUGOUT SITE PLAN: THE PLAN INDICATES A 36'-0" SLAB DIMENSION, BUT SHOWS THE DIMENSION TO THE DUGOUT STRUCTURE. PLEASE CLARIFY.
2. SHEET A4; DUGOUT DETAILS: THE PLAN VIEW INDICATES A 10'0" X 12'-6" DUGOUT STRUCTURE. THE DUGOUT SITE PLAN INDICATES FOUR SIDE-BY-SIDE UNITS. THIS WOULD TOTAL A 50'-0" STRUCTURE WIDTH (4 AT 12'-6"). PLEASE CLARIFY.
3. SHEET A4; DUGOUT STRUCTURE: STRUCTURAL CALCULATIONS MUST BE PROVIDED FOR THE LATERAL/UPLIFT ANALYSIS ON THE DUGOUT. ANCHORS AND FOUNDATIONS MUST BE DESIGNED AND SUBMITTED BY A LICENSED ENGINEER OR ARCHITECT, WITH DETAILS INDICATED ON THE DRAWINGS AS REQUIRED.
4. SHEET S1; SHELTER FOUNDATION PLAN 1: STRUCTURAL CALCULATIONS MUST BE PROVIDED FOR THE LATERAL ANALYSIS ON THE SHELTER BUILDING. ANCHORS AND FOUNDATIONS MUST BE DESIGNED AND SUBMITTED BY A LICENSED ENGINEER OR ARCHITECT.
5. SHEET S1; FOUNDATION SECTION 2: A NOTE ON THE LEFT INDICATES TO 'REFERENCE DETAIL 2' FOR CONCRETE ANCHORING. PLEASE REVISE THAT REFERENCE.
6. SHEET S1; FOUNDATION SECTION 2: A NOTE ON THE RIGHT INDICATES THE DEPTH OF THE FOUNDATION AS 'PER CODE'. PROVIDE THAT DEPTH (BASED ON THE GEOTECHNICAL REPORT) ON THE DETAIL.
7. SHEET S2 (CMU WALL DETAIL 3); STRUCTURAL CALCULATIONS: THE CALCULATIONS (SECOND PAGE) OF THE BLOCK WALL DESIGN PARAMETERS INDICATE AN 8" WALL THICKNESS, WHILE THE DETAIL SHOWS A 12" CMU WALL. PLEASE CLARIFY.
8. SHEET S2; CMU WALL DETAIL 3: PROVIDE STRUCTURAL CALCULATIONS FOR THE WALL FOUNDATION, AND INDICATE THAT DESIGN ON DETAIL 3.
9. GENERAL: SINCE THIS IS A NEW POLE AND FOUNDATION, PROVIDE DETAILS ON THE FULL SIZE DRAWINGS FOR THE POLE, BASE PLATE, ANCHOR BOLTS, AND FOUNDATION.
10. GENERAL: PLEASE PROVIDE TWO COMPLETE SETS OF ALL STRUCTURAL CALCULATIONS (POLE AND FOUNDATION, WALL AND FOUNDATION, SHELTER FOUNDATION AND ANCHORS, AND DUGOUT FOUNDATION AND ANCHORS).
11. GENERAL: ON THE DRAWINGS, PROVIDE A CODE ANALYSIS SHEET FOR SPECIFIC CODES USED AND MATERIAL SPECIFICATIONS (CONCRETE, MASONRY, REINFORCING STEEL, ALLOWABLE SOIL BEARING, POLE STEEL, ANCHOR BOLTS, DUGOUT STEEL, ETC.).
12. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
03/17/2015 CPIERCE1 COMMUNICATIONS REVIEW Completed PER JEFFREY SELIGMAN
03/18/2015 MICHAEL ST. PAUL PLANNING-CITY HALL REVIEW Approved
03/18/2015 MICHAEL ST. PAUL ZONING REVIEW Approved
03/27/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide the following information to ensure a safe and code compliant electrical installation of equipment.
#1. Plan sheet E4.
(a).The voltage for the meter base is not consistent in relation to the main service disconnecting means.
(b). Indicate conduit, conductor sizes and types between the 50 kva transformer and the 200 amp disconnect switch.
(c). Panel VZW not shown on the one line.
(d). Specify all fuse types and sizes for disconnects.
#2. Show compliance with the City of Tucson Outdoor Lighting Code.
#3. City of Tucson policy requires all new electrical service installations to be fed underground. A waiver may be obtained on line or at PDSD office at 201 N. Stone ,8AM-4PM . M-F.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/13/2015 AROMERO4 OUT TO CUSTOMER Completed