Review Details: RESUBMITTAL
Permit Number - T15CM01066
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/27/2015 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. As per the written agreement with the building official, Mr. Chris Kiel dated 3/18/2015, a maximum occupant load of 300 will be allowed for a temporary CofO with the enlargement of the toilet rooms. a. Please remove all occupant load references on sheet A001 and provide a reference to this agreement with a maximum occupant load of 300. 2. Also stated in the agreement, the basement is to be used for storage only. Please include this restriction on the plans as a reference note. 3. Please explain the intent of "A temporary stage". If a raised stage is to be constructed, please provide structural framing details and calculations. If a raised manufactured stage is to be provided, please provide manufacturer's specifications and catalog information. 4. Previous comments with no response: a. Previous Comment 1: Provide a site plan b. Previous comment 7: Show the heights of the water dispenser spouts as per The 2012 IBc, Section 1109.5 and ICC A117.1, Section 602.4 c. Previous Comment 3: Please provide structural details and calculations of the support platform for the 30 gallon water heater. END OF REVIEW |
| 06/02/2015 | CPIERCE1 | WWM | REVIEW | Completed |