Permit Number: T15CM01017
Parcel: 99999999A

Address:
4146 N ORACLE RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T15CM01017
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/17/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change #1. Equipment ground for 400 amp feeder required to be #1 (AL) min. Per 250.122 NEC.
#2. Grounding electrode system for new and existing service shall be common Per 250.58 NEC.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/19/2015 AROMERO4 OUT TO CUSTOMER Completed