Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T15CM01013
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/11/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. PREVIOUS COMMENT 5: DETAIL 12 ON SHEET S-4 STILL INDICATES A 4X4X14 GA. COLUMN. PLEASE REVISE TO MATCH SHEET S-3. 2. PREVIOUS COMMENT 15: ON SHEET S-2 (SECTION A-A AND NORTH AND SOUTH ELEVATION) PLEASE INDICATE THE SECOND VERTICAL MEMBER SIZE ON THE DRAWING. 3. SHEET S-4; DETAIL 2: A NOTE INDICATING 'COLUMN' IS POINTING TO THE FLOOR SLAB. PLEASE REVISE. 4. PREVIOUS COMMENT 11: IT IS STILL NOT CLEAR ON THE DETAIL WHAT THE 1/2" DIAMETER ANCHOR BOLTS AT 24" OC ARE CONNECTING. IS IT THE RAFTER TO THE WALL? PLEASE CLARIFY ON THE DETAIL. 5. PREVIOUS COMMENT 19: THE STRUCTURAL TUBE 5X5X3/8 IS STILL INDICATED IN THE CALCULATIONS ON SHEET 9. PLEASE CLARIFY TO MATCH THE DRAWINGS. 6. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |