Permit Number: T15CM00998
Parcel: 138070650

Address:
825 W MOSSMAN ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T15CM00998
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/19/2015 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T15CM00998
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

STRUCTURAL PLANS:

1. The integrity of staggered nailing is incomplete without nail size and minimum edge spacing per Table R602.3(1). Update detail #3/4, or consider glu-lam beams for the back porch.

SECTIONS - DETAILS - NOTES:

1. Identify each Section on sheet #5 consistent with plan references, R106.
2. Calculate and show the attic ventilation using 1 to 150 of attic area in compliance with R806.2. Provide appropriate upper and lower space vents when applying the reduced area calculation. Update the roof vent calculation changing 300 to 150 on sheet #4.
3. Notate and size all roofing drains and scuppers for flat roofed areas, R903.4. A 4" minimum width is required for the area served at a 3 in/hr rainfall rate, IPC 1107.3.

MECHANICAL PLANS:

1. All code references are to the 2012 International Residential Code. Update note #15 sheet 6.
2. Show combustion air compliance for appliances in confined spaces with two interior area openings of 1 SQ IN for each 1,000 BTU rating and minimum of two 100 SQ IN openings, one within 12" of top and other 12" of bottom, G2407.5.3.1. Update the vent size shown on sheet 6.

ELECTRICAL PLANS:

1. Show or notate the mast height on the electrical service riser providing 8' clearance above the Porch roof, E3604.2.1.
2. Clarify the 240 volt circuits serving the dryer on sheet 6, E3705.5.
3. Show one 20 AMP branch circuit in the laundry area (circuit #13), E3703.3 and 3901.8.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing is U=0.40, skylights U=0.65, ceiling R=38 and walls R=13. Update the maximum "U" factors of the windows shown at note #8, sheet 2, N1102.1.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/26/2015 CPIERCE1 REJECT SHELF Completed