Review Date Reviewer's Name Type of Review Description Status Comments
05/31/2016 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: 4973 E. Speedway Blvd
T15CM00996
Building Plan (1st Review)

TRANSMITTAL DATE: May 31, 2016

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The building plans cannot be approved until development package, DP15-0021, has been approved.

3. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
05/31/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
05/31/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. GENERAL: THIS PROJECT IS MISSING A SITE PLAN AND CODE ANALYSIS. PLEASE INCLUDE ON THE DRAWINGS.
2. GENERAL: PLEASE INCLUDE THE OCCUPANCY LOAD ALONG WITH PLUMBING FIXTURE REQUIREMENTS ON THE DRAWINGS FOR THE ADDITION ONLY.
3. GENERAL: PLEASE INCLUDE STRUCTURAL MATERIAL STRENGTHS USED ON THIS PROJECT (CONCRETE, REINFORCING, WOOD, ETC.).
4. GENERAL: PLEASE INCLUDE ON THE DRAWINGS AN ANALYSIS FOR FIRE RESISTANCE REQUIREMENTS OF THE ADDITION PER THE IBC TABLES 601 AND 602.
5. SHEET 2; NOTE 8: PLEASE INCLUDE AN ANALYSIS ON THE PLANS FOR THE ALLOWABLE AREA OF THIS ADDITION AND TOTAL AREA OF ALL BUILDINGS. THIS WILL INCLUDE THE SEPARATION OF THE ADDITION FROM THE EXISTING BUILDING (IF REQUIRED: SEE TABLE 503). IS THE WEST WALL OF THE ADDITION REQUIRED TO BE A ONE HOUR FIRE RATED WALL PER NOTE 8?
6. STRUCTURAL CALCULATIONS: THE SECOND PAGE OF THE CALCULATIONS ARE BASED ON THE 2006 IBC REQUIREMENTS. PLEASE REVISE THOSE CALCULATIONS TO MEET THE 2012 IBC.
7. STRUCTURAL CALCULATIONS: THE THIRD PAGE OF THE CALCULATIONS INDICATES THE 2012 IBC CODE WAS USED. PLEASE VERIFY.
8. STRUCTURAL CALCULATIONS: THE FIFTH PAGE OF THE CALCULATIONS DESIGNS THE SHEAR WALLS BASED ON THE 2006 IBC TABLE 2306.4.1. PLEASE REVISE.
9. STRUCTURAL CALCULATIONS AND DRAWINGS: IT APPEARS THE NORTH AND EAST WALLS INCLUDE A LOWER MASONRY WALL WITH A WOOD STUD WALL ABOVE. PROVIDE CALCULATIONS FOR THE SHEARWALLS USING A COMBINATION OF THE WOOD AND MASONRY CONSTRUCTION.
10. GENERAL: AT THIS TIME, A COMPLETE BUILDING AND STRUCTURAL REVIEW CAN NOT BE COMPLETED DUE TO THE LACK OF PLANS, DETAILS, INFORMATION, AND CHANGING CODE REQUIREMENTS INDICATED. ADDITIONAL COMMENTS NOT INCLUDED IN THIS REVIEW MAY BE ADDED DURING THE NEXT REVIEW CYCLE.
11. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
06/01/2016 PAUL BAUGHMAN ENGINEERING REVIEW Reqs Change DP must be approved first.
06/02/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved